Customization: | Available |
---|---|
Certification: | ISO9001, CE |
Shell Material: | Stainless Steel |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
project | unit | C module load switch unit | Fmodule load switch -fuse combination electric unit | V breaker unit | |
rated voltage | kv | 12 | 12 | 12 | |
rated current | A | 630 | 125(note 10 | 630 | |
1min power frequency withstand voltage | phase to ground/phase to phase | kv | 42 | 42 | 42 |
fracture | kv | 48 | 48 | 48 | |
impact withstand voltage | phase to ground/phase to phase | kv | 75 | 75 | |
fracture | kv | 85 | 85 | ||
rated closed loop breaking current | A | 630 | |||
rated cable charging breaking current | A | 30 | |||
rated breaking inductive current | A | (note 2)) | |||
rated short time withstand current 3s | ka | 20 | 20 | ||
rated withstand current peak | kA | 50 | 1700 | 50 | |
rated transfer current | A | (note 3) | |||
rated short circuit breaking current | KA | 20 | |||
rated short circuit making current | KA | 50 | |||
rated short circuit breaking times | time | 30 | |||
rated short circuit losing times(load switch/ground switch) | times | 5/5 | |||
rated current breaking times | time | >100 | |||
times of mechanical operations | time | 5000/2000 | 5000/2000 | 3000 |