| Customization: | Available |
|---|---|
| Breaking Capacity: | High Voltage Circuit Breakers |
| Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
| name | unit | data |
| rated voltage | KV | 40.5 |
| rated current | A | 630/1250 |
| rated frequency | HZ | 50/60 |
| power frequency withstand voltage 1min(wet)(dry)phase to phase/phase to ground | KV | 80 95/95 |
| lighting impulse withstand current(peak value) phase to phase/phase to ground | KV | 185 |
| rated short circuit breaking current | KA | 25/31.5 |
| rated short circuit closing current(peak) | KA | 63/80 |
| rated peak withstand current | KA | 63/80 |
| 4s short time withstand current | KA | 25/31.5 |
| rated operating cycle | on-0.1s-on/off-3s-on/off-6s on/off-60s recovery | |
| rated short circuit current breaking times | TIMES | 30 |
| mechanical life | TIMES | 10000 |
| mechanism control voltage | V | AC/DC220 |
| 1min power frequency withstand voltage of secondary circuit | KV | 2 |
| contact opening distance | MM | 16±1 |
| contact overstroke | MM | 4±0.5 |
| opening speed | M/S | 1.4-1.8 |
| closing speed | M/S | 0.4-0.8 |
| contact closing bounce time | MS | ≤5 |
| interphase center distance | MM | 460±2 |
| different periods of three phase opening and closing | MS | ≤2 |
| resistance of each phase conductive loop | μΩ | <80 |
| closing time | MS | ≤100 |
| opening time | MS | ≤50 |
| weight | KG | 270 |