Indoor HV Vacuum Circuit Breaker
Product Description
VS1 indoor medium voltage Vacuum Circuit Breaker is a three-phase AC 50Hz ,rated voltage 6KV,12KV,24KV switch equipment of power system.
Breaker adopts the integral design of the actuating mechanism and the breaker body, which can be used as a fixed installation unit or as an individual VCB carriage together with handcart. They have a long life expectancy. There is no adverse effect on the vacuum, even from frequent switching of operating and short-circuit currents.
Features
1 - with reliable interlock functions, suitable for frequent operation
2 - low noise and energy consumed
3 - simple and robust construction.
4 - high operating reliability
5 - mechanical durability of switch : 20000 times, etc
| No. | Item | Unit | Data | |||||||
| 1 | Rated voltage | KV | 12 | 24 | ||||||
| 2 | Clearance between open contacts | mm | 11±1 | 13±1 | ||||||
| 3 | Over travel of moving contact | 3.5±0.5 | 3.5±0.5 | |||||||
| 4 | Three poles asynchronous time at opening | ms | ≤2 | ≤2 | ||||||
| 5 | Moving contact bounce time at closing | ms | ≤2 | ≤2 | ||||||
| 6 | Average opening speed | m/s | 0.9-1.2 | 0.9-1.2 | ||||||
| 7 | Average closing speed | 0.6-0.8 | 0.6-0.8 | |||||||
| 8 | Connecting pressure of close contacts | N | 20kA | 25kA | 31.5kA | 40kA | 20kA | 25kA | 31.5kA | 40kA |
| 2000±200 | 2400±200 | 3100±200 | 4250±200 | 2000±200 | 2400±200 | 3100±200 | 4750±200 | |||
| No. | Item | Unit | Data | |||||
| 1 | Rated voltage | KV | 12 | 24 | ||||
| 2 | Power frequency withstand voltage | 42 | 65 | |||||
| 3 | Lightning impulse voltage(peak value) | 75 | 125 | |||||
| 4 | Frequency | Hz | 50 | 50 | ||||
| 5 | Rated current | A | 630 1250 |
630 1250 1600 2000 2500 3150 | 1250 1600 2000 2500 3150 4000 | 630 1250 |
630 1250 1600 2000 | 1600 2000 2500 |
| 6 | Short circuit breaking current | kA | 20/25 | 31.5 | 40 | 25 | 25/31.5 | 31.5/40 |
| 7 | Thermal stability current | kA | 20/25 | 31.5 | 40 | 25 | 25/31.5 | 31.5/40 |
| 8 | Dynamic stable current | kA | 50/63 | 80 | 100 | 63 | 80 | 100 |
| 9 | Short circuit making current | kA | 50/63 | 80 | 100 | 63 | 80 | 100 |
| 10 | Rated current breaking time | Times | 20000 | 20000 | ||||
| 11 | Short circuit breaking current times | Times | ≤50 | ≤30 | ||||
| 12 | Operation voltage | V | AC/DC 110/220 | AC/DC 110/220 | ||||
| 13 | Input power | W | 70 | 70 | ||||
| 14 | Storage time | s | ≤15 | ≤15 | ||||
| 15 | 3 phase non-synchronous | ms | ≤2 | ≤2 | ||||
Founded in 2008, registered capital of 108 million CNY, ROOQ electric group.;ltd is a high-tech enterprise specializing in the design, manufacture, sales and service of products such as power transformers, complete sets of electrical appliances, high and low voltage components, and smart city control systems.