Silicon Steel Core Dry Type Cast Resin Transformer

  • Audited Supplier
  • 6 yrs

Contact Supplier

Product Highlights

  • Fireproof & Safe Design: Epoxy resin cast design is non-flammable, self-extinguishing, and oil-free for safe indoor use.
  • High Overload Capacity: Forced air cooling (AF) allows 50% capacity increase for short-term emergency or intermittent overload.
  • Low Loss & Noise: Features low operating loss, low noise, and high working efficiency for energy saving.
  • Smart Temperature Control: Equipped with intelligent temperature detection system, auto fan control, alarms, and IS485 interface.
  • Customizable Parameters: Capacity, HV/LV voltage, and winding material (Cu/Al) are customizable to specific needs.
  • Strong Short-Circuit Resistance: High mechanical strength and strong short-circuit resistance ensure long service life and reliability.
  • Compact & Lightweight: Small volume and light weight reduce space requirements and lower installation costs.
  • Multiple Certifications: Complies with ISO9001, CCC, UL, IEC60076, and GB/T1094.11 standards.

Product Images of Silicon Steel Core Dry Type Cast Resin Transformer

Silicon Steel Core Dry Type Cast Resin Transformer
Silicon Steel Core Dry Type Cast Resin Transformer pictures & photos
Silicon Steel Core Dry Type Cast Resin Transformer
Silicon Steel Core Dry Type Cast Resin Transformer pictures & photos
Silicon Steel Core Dry Type Cast Resin Transformer
Silicon Steel Core Dry Type Cast Resin Transformer pictures & photos
Silicon Steel Core Dry Type Cast Resin Transformer
Silicon Steel Core Dry Type Cast Resin Transformer pictures & photos
Silicon Steel Core Dry Type Cast Resin Transformer
Silicon Steel Core Dry Type Cast Resin Transformer pictures & photos
Silicon Steel Core Dry Type Cast Resin Transformer
Silicon Steel Core Dry Type Cast Resin Transformer pictures & photos
Silicon Steel Core Dry Type Cast Resin Transformer
  • Silicon Steel Core Dry Type Cast Resin Transformer
  • Silicon Steel Core Dry Type Cast Resin Transformer
    Silicon Steel Core Dry Type Cast Resin Transformer
  • Silicon Steel Core Dry Type Cast Resin Transformer
    Silicon Steel Core Dry Type Cast Resin Transformer
  • Silicon Steel Core Dry Type Cast Resin Transformer
    Silicon Steel Core Dry Type Cast Resin Transformer
  • Silicon Steel Core Dry Type Cast Resin Transformer
    Silicon Steel Core Dry Type Cast Resin Transformer
  • Silicon Steel Core Dry Type Cast Resin Transformer
    Silicon Steel Core Dry Type Cast Resin Transformer
  • Silicon Steel Core Dry Type Cast Resin Transformer
    Silicon Steel Core Dry Type Cast Resin Transformer

Find Similar Products

Product Description

Silicon Steel Core Dry Type Cast Resin Transformer
Cast Resin  transformr
Product Description


SCB series dry type transformers refer to transformers in which the core and windings are not immersed in insulating oil. The cooling methods are divided into natural air cooling (AN) and forced air cooling (AF). When natural air cooling, the transformer can run continuously for a long time under the rated capacity. When forced air cooling, the output capacity of the transformer can be increased by 50% in short time. It is suitable for intermittent overload operation or emergency accident overload operation; due to the large increase in load loss and impedance voltage during overload, it is in an uneconomic operation state, so it should not be kept in continuous overload operation for a long time.
 

1.Power Capacity: 30-16000KVA

2.Voltage Level: 10KV,20KV,35KV or Others

3.Type of Voltage Regulation: Off-circuit or On-Ioad

4.Tapping Range: ±5 %  ±2x2.5 % ±4x2.5 %

5.Frequency: 50Hz or 60Hz

6.Phases: Three or Single

7.Connection Symbol: Dyn11,Yyn0 ( or as requested)

8.Short- circuit Impedance:  Standard Impedance

9.Maxmun Temperature Rise: 100K

10.Insulation Class:Class F or H

11.Protection Class:IP00/IP20/IP23/IP40/IP50

12.Altiude is not exceeding 1000m,ambient temperature not exceeding 40OC. If it can't meet such conditions,we will modulate parameters in accordance with standard.

 

Features:

Since epoxy resin is a non-flammable, flame-retardant, self-extinguishing solid insulating material, safe and clean, epoxy resin cast dry-type transformers are oil-free, non-flammable, and have low operating loss, strong short-circuit resistance, less maintenance work, high working efficiency, small volume and low noise. It is often used in places with high performance requirements such as fire prevention and explosion protection, and has the following practical characteristics:
1.It is safe,fireproof,pollution-free,and can be directly operated in the load center;
2.High mechanical strength,strong short-circuit resistance,small partial discharge,good thermal stability,high reliability and long service life;
3.Low loss,low noise,obvious energy saving effect,maintenance-free;
4.Good heat disspation performance ,and capacity operation can be increased in short time when forced air cooling;
5.Good moisture resistance;
6.Dry-type transformers can be equipped with a complete temperature detection and protection system.Using intelligent signal temperature control system, it can automatically detect and display the respective operating temperatures of the three-phase windings, can automatically start and stop the fan, and have functions such as alarms and trips. IS485 communication interface can be installed to realize wireless detection and intelligent management.

7.Small size, light weight, less space and low installation cost.

 
Standard:
IEC60076, GB/T1094.11, GB/T17211.


Applicable Environment:
1.0-40 (ºC), relative humidity <70%;
2.Altitude: no more than 2500 meters;
3.Avoid rain, humidity, high temperature, high heat or direct sunlight. 
4.Prevent working in places where there are more corrosive liquids, or gases, dust, conductive fibers or metal fines;
5.Prevent working in vibration or electromagnetic interference places;
6.Avoid long-term storage and transportation upside down, and avoid strong impact.
 

Technical Parameter:

Rated capacity kVA Voltage tap range Connection symbol No-load loss kW Load loss kW No-load current % Short circuit impedance %
HV  kV HV tap range % LV  kV 130ºC(B)(100ºC) 155ºC(F)(120ºC) 180ºC(H)(145ºC)
SCB10-50 11
15
20
33
±2.5
±5
0.4 Dyn11
Yyn0
0.35 1.17 1.23 1.30 2 6
SCB10-100 0.54 1.87 1.99 2.13 1.8
SCB10-160 0.66 2.35 250 2.64 1.5
SCB10-200 0.73 2.77 2.94 3.14 1.5
SCB10-250 ±2×2.5
±5
0.85 3.22 3.42 3.66 1.3
SCB10-315 0.96 3.85 4.08 4.36 1.3
SCB10-400 1.15 4.65 4.84 5.20 1.1
SCB10-500 1.35 5.46 5.79 6.19 1.1
SCB10-630 1.53 6.45 6.84 7.32 1
SCB10-800 1.74 7.79 8.26 8.85 1
SCB10-1000 2.07 9.22 9.77 10.4 0.85
SCB10-1250 2.38 10.8 11.5 12.3 0.85
SCB10-1600 2.79 13 13.8 14.8 0.85
SCB10-2000 3.24 15.4 16.3 17.5 0.7
SCB10-2500 3.87 18.2 19.3 20.7 0.7
SCB10-2000 3.24 16.8 17.8 19.1 0.7 8
SCB10-2500 3.87 20 21.2 22.7 0.7

 

Silicon Steel Core Dry Type Cast Resin TransformerSilicon Steel Core Dry Type Cast Resin TransformerSilicon Steel Core Dry Type Cast Resin TransformerSilicon Steel Core Dry Type Cast Resin TransformerSilicon Steel Core Dry Type Cast Resin TransformerSilicon Steel Core Dry Type Cast Resin TransformerSilicon Steel Core Dry Type Cast Resin TransformerSilicon Steel Core Dry Type Cast Resin Transformer
Silicon Steel Core Dry Type Cast Resin Transformer

About the Supplier

This supplier has been audited by BV. Verify the report on the official BV website with ID "MIC-ASI2031767". Items marked "verified" are certified.

ROOQ ELECTRIC GROUP CO., LTD.
ROOQ ELECTRIC GROUP CO., LTD.
ROOQ ELECTRIC GROUP CO., LTD.
ROOQ ELECTRIC GROUP CO., LTD.
ROOQ ELECTRIC GROUP CO., LTD.
ROOQ ELECTRIC GROUP CO., LTD.
ROOQ ELECTRIC GROUP CO., LTD.
ROOQ ELECTRIC GROUP CO., LTD.

About Our Factory & Business Background

verified Business Type
Manufacturer/Factory & Trading Company
Address
No. 231 Jing 7 Road, Economic Development Zone, Yueqing Zhejiang Province, Wenzhou, Zhejiang, China
verified Plant Area
5000 square meters
verified Number of Employees
103
verified Registered Capital
108,000,000 RMB
verified Terms of Payment
LC, T/T
verified International Commercial Terms(Incoterms)
FOB, CIF, CFR
verified Average Lead Time
Peak Season Lead Time: within 15 workdays
Off Season Lead Time: within 15 workdays
verified Nearest Port
Ningbo Port

Our Production Capability & Technical Expertise

verified Main Products
High Voltage Switchgear, Low Voltage Switchgear, Transformer, Distribution Box, Arrester, Disconnector, Fuse, Vacuum Circuit Breaker
verified Production Machines
Bench Drill, Cutting Facility, Oven, Pouring Furnace, Winding Facility, Bus Bar Facility
verified ODM Service Available
Yes
verified OEM Service Available
Yes
verified R&D Engineers
15 people
verified Own Brand
Yes

Our Industry Experience & Global Business Record

verified Year of Establishment
2014-05-30
Export Year
2009-04-15
verified Main Markets
Africa, Domestic, Central Asia
verified Number of Foreign Trading Staff
5
verified Overseas Agent/Branch
No

Our Certifications, Standards & Industry Recognition

verified Product Certification
CE, Others

FAQ

What is the rated capacity range?
The rated capacity ranges from 30kVA to 4000kVA, with standard models available up to 16000KVA.
Can the transformer handle overload conditions?
Yes, it supports intermittent or emergency overload. Forced air cooling (AF) can increase output capacity by 50% for short periods.
What are the available voltage levels?
Standard HV levels include 6kV, 6.6kV, 11kV, 15kV, 22kV, 33kV, and 35kV. LV is typically 0.4kV or 0.38kV.
Is customization available for this transformer?
Yes, capacity, voltage levels, and winding material (Copper or Aluminum) can be customized. Connection symbols like Dyn11 or Yyn0 are also available as requested.
What is the warranty and support policy?
The product comes with certifications including ISO9001, CCC, and UL. Technical support includes intelligent temperature monitoring and alarm systems.
What cooling methods are supported?
It supports natural air cooling (AN) for continuous rated operation and forced air cooling (AF) for increased short-term capacity.
What insulation class is used?
The transformer uses Class F or Class H insulation, with maximum temperature rise of 100K.

Send your message to this supplier

Contact Information
Recipient
Message

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now