Supply Oil Immersed Distribution Power Transformer
Contact Supplier
Product Highlights
- Hermetically Sealed Design: Elastic tank prevents oil oxidation and moisture absorption, ensuring ideal liquid condition.
- Wide Power Range: Available in ratings from 30 kVA to 2500 kVA for various power needs.
- Customizable Vector Groups: Dyn5, Yd11, and other vector groups can be customized to specific requirements.
- Dual Voltage Capability: Can be supplied with two primary voltages or two simultaneous secondary voltages.
- CRGO Core Material: Uses oriented grain silicon steel for low loss and guaranteed noise levels.
- IEC/BSEN 60076 Compliant: Designed and tested according to international standards for safety and performance.
- Low Maintenance System: No drier or air breather required, reducing maintenance needs and leak risks.
- OEM and ODM Services: Full customization available including brand, specifications, and design.
Product Attributes
- Customization
- Available
- Application
- Power, Lighting
- Phase
- Three
- Model NO.
- 100kVA
- Core
- Core-type Transformer
- Cooling Method
- Oil-immersed Type Transformer
- Winding Type
- Two-winding Transformer
- Certification
- ISO9001-2000, ISO9001, CCC, CE
- Usage
- Combined Transformer, Power Transformer, Distribution Transformer
- Frequency Characteristics
- Power Frequency
- Shape of Core
- EI
- Brand
- Rooq
- Transport Package
- Wooden Case
- Specification
- 1000*655*895mm
- Trademark
- ROOQ
- Origin
- China
- HS Code
- 850422
- Production Capacity
- 500PCS/Month
Product Images of Supply Oil Immersed Distribution Power Transformer
Find Similar Products
Product Description
Transformers immersed in insulating fluid with natural self cooling (ONAN), three-phase, 50/60 Hz.
For indoor or outdoor use.
Hermetically sealed, CRGO Silicon steel, High-strength cold-rolled steel tank.
Standard
The transformers described in this catalogue are designed and tested in accordance to IEC/BSEN 60076.
Features
Common power ratings:
30, 50, 80,100,125,160, 200, 250, 315, 400, 500, 630, 800, 1000, 1250, 1600, 2000, 2500 kVA.
This transformer is designed for voltages of ≤ 36 kV. Specific figures are not given for this parameter because of the wide variety of voltages used. Transformers can be supplied on demand to run at two different primary voltages, the shift between these input voltages has two
basic alternatives:
• with a primary tap changer which can be switched with no load and no applied voltage
• or by changing terminals under the cover.
The secondary voltage under no load is allocated at 400V, 415V, 433V, though other voltages can be supplied on demand.
When usage requires two voltages, transformers with two simultaneous voltages can be supplied. In this case the no-load voltages are set to 400V(230V),415V(240V),433V(230V) .
The connections normally used are as follows:
• For rated power levels of 160 kVA or less: Yyn0
• For rated power levels over 160 kVA: Dyn11.
• Dyn5, Yd11 and others can customaized.
As per IEC /BSEN 60076 standards these are
set in accordance with the highest voltage for the material,
being the level immediately above the rated voltage.
| Material maximum admissible voltage | 12kV | 17,5kV | 24kV | 36kV |
| Withstand voltage | 28kV | 38kV | 50kV | 70kV |
| Basic insulation level | 75kV | 95kV | 125kV | 170kV |
As per IEC/BSEN 60076 , in normal operating mode:
• 60º K max. in oil
• 65º K average in windings
Other temperature rise levels on demand.
Transformers covered must have one of the following oil expansion systems:
a) an external conservator tank
b) an air chamber under the cover
c) a hermetically sealed elastic tank
ROOQ recommends option (c), which is the one considered in this catalogue, as it has the following advantages:
1.Smaller size, as there is no need for an conservator tank or air chamber, making for easier transformer transportation and placement.
2.Lower overall weight.
3.Increased sturdiness and less risk of leaks, there being no weak points such as welds between the expansion tank and the cover, oil level gauge, Silicagel air breather, etc.
4.Low maintenance due to the absence of elements such as the drier, over-pressure valves and liquid level indicators.
5.No degradation of insulating liquid (oil) by oxidation or absorption of moisture, as there is no contact with the air. The liquid therefore remains in ideal condition.
6.Better conservation of seals due to lack of contact with air, which means that they stay more flexible.
Construction details
I- MAGNETIC CIRCUIT
Oriented grain, very low loss magnetic plate is used following IEC/BSEN 60076. The type or class of plate is chosen on the basis guaranteed noise level and losses. The net cross section is maintained constant in limbs and yokes throughout the magnetic circuit, as a special configuration does away with the need for cross-section reducing grip bolts (section reduction).
The limbs and yokes are joined by 45º lugless joints, with complete one-piece yoke, and stacking is arranged so that each plate profile is staggered with regard to the previous one, thus minimising the effect of the gap. The profile is stepped, with the number of steps required to obtain the best coefficient of useful surface area.
II- LOW VOLTAGE WINDING
This winding is located next to and concentric with the magnetic circuit. Two clearly different types of wire are used depending on the allocated current:
- Rectangular cross-section with rounded edges.
- Strips with conditioned edges.
In the former case each wire is insulated with thermal class A cellulose paper or class H enamel. Strips are used bare.
The rectangular wire winding is set up in a complete layer configuration with one or more concentric channels for cooling.
The insulation between layers is always B status resin impregnated.
The width of the strip on strip type winding with conditioned edges covers the whole axial width of the coil, so that each turn is a layer of winding. As the strip is wound a layer of type B resin impregnated paper is wound with it. This polymerises during the drying cycle, giving the winding the strength to withstand the mechanical stresses entailed by short circuits as per IEC 60076 standards.
III- HIGH VOLTAGE WINDING
This is wrapped around the low voltage winding to lie concentric with it, separated by an insulation structure giving the level of insulation desired.
The conductors used are of two types:
• circular cross-section wire
• rectangular cross section strips.
The conductors are insulated with thermal class H enamel. The rectangular section wires or strips have thermal class A paper or thermal class H enamel. With both types of wire, the winding configuration is anti-resonant in one section, making it highly resistant to ray type pulse waves.
The insulation between layers is resin impregnated, polymerising during drying to give the winding the strength to withstand the mechanical stresses entailed by short circuits.
IV- ACTIVE PART
This is the name given to the set of elements which can be removed from the tank of the transformer. Apart from the core and windings,the main elements are:
• fixing and guide structure
• tap changer
• cover
• cover bushing
V- TANK
The distribution transformer tank is elastic, enabling it to absorb the increase in volume of insulating fluid as it heats up due to the transformer operation without experiment permanent deformations. It comprises the following components:
• supporting frames
• base
• cooling fins
• outer frame
- The supporting frames are welded to the base in a continuous, watertight bead to prevent rusting. They have holes for attaching wheel heads and dragging the transformer.
- The base is bath shaped, with earth connections and a drainage device on the sides.
- The cooling fins are the fundamental part of the tank: they form the corrugated side walls and give it the required elasticity.They are made of cold-rolled steel plate between 1 and 5 mm thick, bent without drawing. Elasticity is obtained by a suitable combination of height, depth, plate thickness and resulting internal pressure.
- The outer frame of the tank is made of L-section steel, welded to the top of the corrugated side walls. The top of this frame houses the pressure limiters for the seal and bear the holes for the cover/tank fixing screws.
The two tables below indicate the guaranteed rated figures as per IEC60076 standards.
These figures are valid for a single secondary voltage, even if there is more than one primary voltage.
Highest voltage for material: ≤ 12 kV
| Rated capacity (kVA) | H.V. (kV) |
Tapping range | L.V. (kV) | Vector group | Loss(kW) | No-load current (%) | Impedance voltage (%) | Weight (kg) | ||
| Load loss | No-load loss | oil | Total | |||||||
| 10 | 6 10 11 | ±5% or ±2*2.5% | 0.4 0.415 0.433 | Dyn11 or Yyn0 | 0.26 | 0.09 | 3.2 | 4 | 45 | 172 |
| 20 | 0.44 | 0.10 | 3.0 | 65 | 240 | |||||
| 30 | 0.63 | 0.13 | 2.3 | 65 | 245 | |||||
| 50 | 0.91 | 0.17 | 2.0 | 80 | 330 | |||||
| 63 | 1.09 | 0.20 | 1.9 | 90 | 365 | |||||
| 80 | 1.31 | 0.25 | 1.9 | 95 | 410 | |||||
| 100 | 1.58 | 0.29 | 1.8 | 115 | 490 | |||||
| 125 | 1.89 | 0.34 | 1.7 | 140 | 620 | |||||
| 160 | 2.31 | 0.40 | 1.6 | 155 | 720 | |||||
| 200 | 2.73 | 0.48 | 1.5 | 175 | 810 | |||||
| 250 | 3.20 | 0.56 | 1.4 | 200 | 940 | |||||
| 315 | 3.85 | 0.67 | 1.4 | 215 | 1090 | |||||
| 400 | 4.52 | 0.80 | 1.3 | 240 | 1250 | |||||
| 500 | 5.41 | 0.96 | 1.2 | 285 | 1460 | |||||
| 630 | 6.20 | 1.20 | 1.1 | 4.5 | 345 | 1720 | ||||
| 800 | 7.50 | 1.40 | 1.1 | 390 | 2050 | |||||
| 1000 | 10.30 | 1.70 | 1.0 | 460 | 2430 | |||||
| 1250 | 12.00 | 1.95 | 1.0 | 550 | 2850 | |||||
| 1600 | 14.50 | 2.40 | 0.8 | 690 | 3600 | |||||
| 2000 | 18.00 | 2.60 | 0.7 | 790 | 4300 | |||||
Highest voltage for material: 15-24 kV
| Rated capacity(kVA) | H.V. (kV) | Tapping range | L.V. (kV) | Vector group | Loss(kW) | No-load current (%) | Impedance voltage (%) | Weight (kg) | ||
| Load loss | No-load loss | oil | Total | |||||||
| 30 | 15 20 | ±5% or ±2*2.5% | 0.4 0.415 0.433 | Dyn11 or Yyn0 | 0.60 | 0.10 | 2.1 | 4 | 85 | 350 |
| 50 | 0.87 | 0.13 | 2.0 | 90 | 480 | |||||
| 63 | 1.04 | 0.15 | 1.9 | 110 | 600 | |||||
| 80 | 1.25 | 0.18 | 1.8 | 110 | 660 | |||||
| 100 | 1.50 | 0.20 | 1.6 | 120 | 700 | |||||
| 125 | 1.80 | 0.24 | 1.5 | 130 | 800 | |||||
| 160 | 2.20 | 0.29 | 1.4 | 140 | 940 | |||||
| 200 | 2.60 | 0.33 | 1.2 | 160 | 1130 | |||||
| 250 | 3.05 | 0.40 | 1.2 | 180 | 1290 | |||||
| 315 | 3.65 | 0.48 | 1.1 | 230 | 1400 | |||||
| 400 | 4.30 | 0.57 | 1.0 | 250 | 1550 | |||||
| 500 | 5.15 | 0.68 | 1.0 | 260 | 1780 | |||||
| 630 | 6.20 | 0.81 | 0.9 | 4.5 | 320 | 2100 | ||||
| 800 | 7.50 | 0.98 | 0.8 | 350 | 2560 | |||||
| 1000 | 10.30 | 1.15 | 0.7 | 450 | 2800 | |||||
| 1250 | 12.00 | 1.36 | 0.6 | 490 | 3200 | |||||
| 1600 | 14.50 | 1.64 | 0.6 | 640 | 4000 | |||||
| 2000 | 17.14 | 1.94 | 0.6 | 800 | 4900 | |||||
| 2500 | 20.26 | 2.30 | 0.5 | 1180 | 6300 | |||||
Highest voltage for material: 36 kV
| Rated capacity(kVA) | H.V. (kV) | Tapping range | L.V. (kV) | Vector group | Loss(kW) | No-load current (%) | Impedance voltage (%) | Weightb (kg) | ||
| Load loss | No-load loss | oil | Total | |||||||
| 50 | 30 33 35 38.5 | ±5% or ±2*2.5% | 0.4 0.415 0.433 | Dyn11 Yyn0 Yd11 | 1.27 | 0.21 | 2.0 | 6.5 | 265 | 860 |
| 100 | 2.12 | 0.29 | 1.8 | 310 | 1150 | |||||
| 125 | 2.50 | 0.34 | 1.7 | 320 | 1190 | |||||
| 160 | 2.97 | 0.36 | 1.6 | 360 | 1230 | |||||
| 200 | 3.50 | 0.43 | 1.5 | 390 | 1300 | |||||
| 250 | 4.16 | 0.51 | 1.4 | 425 | 1480 | |||||
| 315 | 5.01 | 0.61 | 1.4 | 460 | 1590 | |||||
| 400 | 6.05 | 0.73 | 1.3 | 490 | 1760 | |||||
| 500 | 7.28 | 0.86 | 1.2 | 540 | 2150 | |||||
| 630 | 8.28 | 1.04 | 1.1 | 620 | 2380 | |||||
| 800 | 9.90 | 1.23 | 1.0 | 780 | 2800 | |||||
| 1000 | 12.15 | 1.44 | 1.0 | 850 | 3410 | |||||
| 1250 | 14.67 | 1.76 | 0.9 | 950 | 3890 | |||||
| 1600 | 17.55 | 2.12 | 0.8 | 1060 | 4620 | |||||
| 2000 | 19.35 | 2.72 | 0.7 | 1195 | 5345 | |||||
| 2500 | 20.70 | 3.20 | 0.6 | 1285 | 5960 | |||||
| 3150 | 24.30 | 3.80 | 0.6 | 7 | 1470 | 6695 | ||||
| 4000 | 28.80 | 4.52 | 0.5 | 1760 | 8350 | |||||
Pictures

About the Supplier
This supplier has been audited by BV. Verify the report on the official BV website with ID "MIC-ASI2031767". Items marked "" are certified.
Company Profile
Established in May, 2014, Zhejiang ROOQ Electric Co., Ltd is a technology-oriented enterprise specializing in R&D, sales and services of power transformers, transformer substation, ring main unit, cable branch box, switchgears, gas insulated cabinates, HV/LV switchgears, high and low voltage switches, wire and cable, LED street light and metal street light poles, telegraph posts of metal ect. It has four professional factories under its jurisdiction: Power Equipment Co., Ltd. Transformer Co., Ltd.; Switchgear Co., Ltd.; Metal fittings Co., Ltd.; Import and export trading company: Zhejiang ROOQ Electric Co., Ltd.
Since its established, our company has been committed to the path of professional development. By virtue of its strong technical force, domestic and foreign advanced equipment, innovative ideas and extensive manufacturing experience, it has been certified by ISO9000 and adopts CAD to provide customers with environment-friendly, energy-saving, low-carbon and high-quality products suitable for regional characteristics to meet the market and the basic requirements of different customers. Now it has become one of the key enterprises in the Chinese manufacturing industry of key transformers and HV/LV switchgears.
Its products cover the national market of China. Also the products are exported to Central Asia, Africa, Southeast Asia, the Middle East, South America and other countries and regions. Based on its complete marketing and service networks, Zhejiang ROOQ Electric Co., Ltd will further expand into the domestic and foreign markets. The company implements a "7*24 service mechanism" and an after-service policy with life-long warranty to actively provide its customers with timely, warm and total services, enhance the product utilization value, premium services and free its customers from any after-sales concerns.
About Our Factory & Business Background
-
Business Type
- Manufacturer/Factory & Trading Company
- Address
- No. 231 Jing 7 Road, Economic Development Zone, Yueqing Zhejiang Province, Wenzhou, Zhejiang, China
-
Plant Area
- 5000 square meters
-
Number of Employees
- 103
-
Registered Capital
- 108,000,000 RMB
-
Terms of Payment
- LC, T/T
-
International Commercial Terms(Incoterms)
- FOB, CIF, CFR
-
Average Lead Time
-
Peak Season Lead Time: within 15 workdays
Off Season Lead Time: within 15 workdays -
Nearest Port
- Ningbo Port
Our Production Capability & Technical Expertise
-
Main Products
- High Voltage Switchgear, Low Voltage Switchgear, Transformer, Distribution Box, Arrester, Disconnector, Fuse, Vacuum Circuit Breaker
-
Production Machines
- Bench Drill, Cutting Facility, Oven, Pouring Furnace, Winding Facility, Bus Bar Facility
-
ODM Service Available
- Yes
-
OEM Service Available
- Yes
-
R&D Engineers
- 15 people
-
Own Brand
- Yes
Our Industry Experience & Global Business Record
-
Year of Establishment
- 2014-05-30
- Export Year
- 2009-04-15
-
Main Markets
- Africa, Domestic, Central Asia
-
Number of Foreign Trading Staff
- 5
-
Overseas Agent/Branch
- No
Our Certifications, Standards & Industry Recognition
-
Product Certification
- CE, Others
FAQ
- What is the maximum voltage for this transformer?
- The transformer is designed for voltages up to 36 kV.
- Can the vector group be customized?
- Yes, Dyn5, Yd11, and other vector groups can be customized according to your needs.
- What are the available power ratings?
- Common power ratings range from 30 kVA to 2500 kVA.
- Is the transformer suitable for indoor and outdoor use?
- Yes, it is designed for both indoor and outdoor applications.
- What cooling method is used?
- It uses natural self-cooling (ONAN) with oil immersion.
- Can the transformer handle two different primary voltages?
- Yes, it can be supplied with two primary voltages using a tap changer or by changing terminals.
- What certifications does the product have?
- The transformer holds ISO9001, CCC, UL, and CE certifications.
- What is the lead time for production?
- The lead time is within 15 workdays for both peak and off-peak seasons.
Send your message to this supplier
People who viewed this also viewed
-
US$100.00-1,000.00 / Piece
-
US$500.00-100,000.00 / Piece
-
US$100.00-1,000.00 / Piece
-
US$100.00-1,000.00 / Piece
-
US$100.00-1,000.00 / Piece
-
US$500.00 / Piece
-
US$500.00-8,000.00 / Piece
-
US$500.00-8,000.00 / Piece
Find Similar Products By Category
- Supplier Homepage
- Products
- Distribution power transformer
- Oil immersed transformer
- Supply Oil Immersed Distribution Power Transformer
Related Categories